Guangdong ALI Testing Equipment Co,.Ltd

GSKA Group Specialized in kinds of PARTS since 1985, Developed and manufactured various generators and generator sets.

Manufacturer from China
Active Member
13 Years
Home / Products / Deep Sea Control Panel /

Automatic Engine Deep Sea Panels , LED Control Module , DSE520

Contact Now
Guangdong ALI Testing Equipment Co,.Ltd
City:dongguan
Province/State:guangdong
Country/Region:china
Contact Person:MissKris
Contact Now

Automatic Engine Deep Sea Panels , LED Control Module , DSE520

Ask Latest Price
Video Channel
Place of Origin :China OEM and UK
Brand Name :GSKA
Model Number :DSE520
MOQ :1-5 pieces
Price :Negotiable
Packaging Details :Standard plywood and wood package.the actual package size against goods size and handle requires. Si
Delivery Time :one weeks on receipt of official sales contract
Payment Terms :L/C,D/P,D/A, Alipay, West Union, TT. Cash,Paypal
Supply Ability :500 pieces per Month
Port :HongKong or ShenZhen,ShangHai,Dalian as required
Package Size :72mm x 144mm x 118.5mm
CertifiCAT-partsion :CE/RoHs/ISO9001
Overall :72*144*118.5mm
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

  1. Model Number :DSE520
  2. Automatic Engine Control Module
  3. Alternator input frequency :50 - 60 hz at rated engine speed.
  4. Maximum operating current : 290 ma at 12 v. 210 ma at 24 v.
  5. Maximum standy current : 50 ma at 12 v. 30 ma at 24 v.
  6. Charge fail excitation range :  0 v to 35 v

We are authorized agent

Deep Sea Electronics PLC The Model 520 is an Automatic Engine Control Module designed to

automatically start and stop the engine.

It will indiCAT-parts-partse the operational status and fault conditions, automatically shut down the engine and indiCAT-parts-partse

the engine failure by a flashing LED on the front panel.

Other simultaneous faults are indiCAT-parts-partsed by steady LED.Selected operational sequences, timers and alarms

can be altered by the customer by using a PC and the 808 interface and software.

This also provides the operator with ‘real-time’ diagnostic facilities to monitor the operation of the system

either locally or remotely.

Remote PC-controlled engine starting and stopping is also featured.Operation of the module is via a three

position rotary switch (key-switch option available) mounted on the front panel with STOP, AUTO and

MANUAL positions.

This allows the module to function with normally open or normally closed switches.

Four fully configurable auxiliary inputs are provided to give protection expansion. These can be selected to

be indiCAT-parts-partsion, warning or shutdown inputs either immediate or held off during start up.

Main features

CONFIGURABLE INPUTS

Configurable inputs are available for:

*Low Oil Pressure

*High Engine Temperature

*Remote Start.

This allows the module to function with normally open or normally closed switches.


Four fully configurable auxiliary inputs are provided to give protection expansion.These can be selected to

be indiCAT-parts-partsion, warning or shutdown inputs either immediate or held off during start up.

ALARM CHANNELS

Multiple alarm channels are provided to monitor the following:


*Under/Overspeed

*Charge Fail

*Emergency Stop

*Low oil pressure

*High engine temperature

*Fail to Start

*Fail to stop

*Loss of speed sensing

*Programmable inputs as selected

First up alarm is indiCAT-parts-partsed by a flashing LED. Subsequent simultaneous alarms are displayed by a steady LED.

SpecifiCAT-parts-partsion

DC SUPPLY

CONTINUOUS VOLTAGE RATING


8 to 35 V Continuous.


CRANKING DROPOUTS


Able to survive 0 V for 50 mS,


providing supply was at least 10 V


before dropout and supply recovers


to 5V. This is achieved without the need for internal batteries.


MAXIMUM OPERATING CURRENT


290 mA at 12 V. 210 mA at 24 V.


MAXIMUM STANDY CURRENT


50 mA at 12 V. 30 mA at 24 V.


CHARGE FAIL EXCITATION RANGE


0 V to 35 V


INPUTS

A;TERNATOR INPUT RANGE


15 - 300 V ac RMS


ALTERNATOR INPUT FREQUENCY


50 - 60 Hz at rated engine speed.


Magnetic Input Range:0.5 V to +/- 70 V (Clamped by transient suppressors)

MAGNETIC iNPUT FREQUENCY


10Hz to 10,000 Hz


OUTPUTS

START RELAY OUTPUT


16 Amp DC at supply voltage.


FUEL RELAY OUTPUT


16 Amp DC at supply voltage.


AUXILLIARY RELAY OUTPUTS


5 Amp DC at supply voltage.


DIMENSIONS

OVERALL


Dimensions: 72mm x 144mm x 118.5mm